Telecom
 Transmission & Distribution
 Special Structures
 Poly Engineering Systems
 Pre Engineered Buildings
 International Business
 
 Poly Engineering Systems
Telecom Shelters
Cold Storage
Defence Shelters
Phase Change Materials (PCM)
 
Phase Change Material in Telecom Shelters
 
  • Use of PCM 29 in telecom shelter can maintain the inside temperature at 25-35 0C up to 6-10 hrs of operation

  • PCM gets charged, when AC is switched on; when the power goes off, it starts discharging i.e. absorbing the heat released by the telecom equipments. Thus it maintains a uniform temperature within the shelter
 

Technical Specifications of PCM 29° C

 

Phase Transition Temperature

29° C

Useful Temperature Range

25° C to 35° C

Latent Heat

185 to 190 kJ/kg

Specific Gravity

1.5

Heat Capacity (Liquid)

2.30 kJ/kg° C

Heat Capacity (Solid)

1.45 kJ/kg° C

Thermal Conductivity (Liquid)

1.0 W/mK

Thermal Conductivity (Solid)

0.8 W/mK

Combustibility

Non Combustible

Toxicology

Non Toxic

Flammability

Non Flammable

Transportability

No hazards for air, sea and road freight

 

Technical Specifications of PCM 25° C

 

Phase Transition Temperature

25° C

Useful Temperature Range

20° C to 30° C

Latent Heat

165 kJ/kg

Specific Gravity

1.5

Heat Capacity (Liquid)

2.30 kJ/kg° C

Heat Capacity (Solid)

1.45 kJ/kg° C

Thermal Conductivity (Liquid)

1.0 W/mK

Thermal Conductivity (Solid)

0.8 W/mK

Combustibility

Non Combustible

Toxicology

Non Toxic

Flammability

Non Flammable

Transportability

No hazards for air, sea and road freight

 
Back to Phase Change Materials (PCM)
 
  © 2010 Aster Private Limited. All Rights Reserved. Sitemap  |  Privacy Policy